Lightning protection: aluminium down-conductor to copper earth
CUPAL strip 500 × 40 × 0.5 mm (the same format as DEHN 562 440) or an M6–M20 washer under an EN 62561-1 tested clamp, where an aluminium down-conductor meets a copper earth conductor. Supplied with an EN 10204 material certificate.
Where the aluminium down-conductor meets the copper earth
A lightning protection system often combines several metals: copper or steel earth electrodes in the ground, aluminium down-conductors on the façade, galvanised or stainless steel fixings on the structure. Where aluminium touches copper directly and the joint gets rain or condensation, the two metals form a galvanic cell and the aluminium side corrodes. The galvanic corrosion guide explains where the potential difference comes from and how to prevent it.
Meanwhile the joint keeps looking sound. The corrosion product, aluminium oxide, is a poor conductor: the clamp is tight, yet the resistance of the earth path rises. The periodic inspection measurement shows it, and so do the stains on the façade. That is why DEHN, among others, sells an Al/Cu Cupal strip for exactly these points.
In short
Where an aluminium down-conductor joins a copper earth conductor, the two metals should not touch. A CUPAL® bimetal strip or washer in the clamp puts its aluminium face to the down-conductor and its copper face to the earth. The clamp stays an EN 62561-1 tested component; CUPAL ships with an EN 10204 material certificate.
- 500 × 40 × 0.5mm
- Stock strip, the DEHN 562 440 format
- 40–150mm
- Custom strip width
- M6–M20
- Washers, 11 sizes from stock
- 24h
- Quote
CUPAL under the tested clamp
CUPAL is cold roll-bonded copper-aluminium bimetal: aluminium on one face, copper on the other, the two layers bonded at the mill. In the joint, the aluminium face of the strip or washer lies against the down-conductor and the copper face against the earth conductor or earth mesh. Like metal meets like metal on both contact faces, so no bare Al/Cu interface remains in the clamp.
Keep the roles apart. EN 62561-1 sets the requirements and tests for lightning protection connection components (connectors, clamps, bonding and bridging components, expansion pieces and test joints); EN 62561-2 does the same for conductors and earth electrodes. The clamp manufacturer runs those tests on its own product. CUPAL strip or washer is not an LPS component; it is an interlayer material under the tested clamp, supplied with an EN 10204 2.2 test report, or a 3.1 inspection certificate on request. The system is still designed by the LPS designer to EN 62305-3.
Stock CUPAL strip is 500 × 40 × 0.5 mm, the same format as the DEHN 562 440 Cupal sheet strip. Wider strip comes in custom widths (40–150 mm) and thicknesses (0.5–2.0 mm), 5–10 working days in production. A joint held by one bolt takes a CUPAL washer, M6–M20. A special shape, such as a pad that fits under a particular clamp, is cut from your drawing.
Outdoors, the cut edge needs attention: on a strip or washer the Al/Cu bond line is exposed there. Put the joint in a protected position or cover the edge, and if the site is salty or very wet, say so in your enquiry. The same joint on boats and masts: copper bonding cable on an aluminium mast.
Replacing DEHN Cupal sheet
Matched by dimensions, not the same make. The DEHN data comes from the DEHN product data sheet and online store.
| DEHN part | DEHN size | Our part | Availability |
|---|---|---|---|
| 562 440 CUPAB 500X40X0.5 AL CU | 500 × 40 × 0.5 mm | CUPAL strip in the same format | From stock, 2–10 working days |
| 562 460 CUPAB 500X60X0.5 AL CU | 500 × 60 × 0.5 mm | CUPAL strip in a custom width (40–150 mm) | Production 5–10 working days |
| Cupal sleeve (CUPAH, e.g. 562 035, 562 050) | Sleeve pushed onto 25–50 mm² conductors | We do not supply sleeves; a washer or cut strip goes into the joint | Most DEHN sleeve variants are marked discontinued in the DEHN store |
Typical Al/Cu points in lightning protection
Four places where aluminium meets copper on the lightning path.
Aluminium down-conductor → copper earth conductor at the test joint
The problem you need to solve. The aluminium down-conductor on the façade joins a copper earth conductor at the test joint or where it enters the ground. The joint is outside and gets rain and condensation.
How CUPAL solves it. CUPAL strip or washer under the tested clamp, aluminium face towards the down-conductor. Keep the clamp and the joint protected and the edge of the strip covered.
Aluminium equipment enclosure or support frame → copper equipotential bonding
The problem you need to solve. An aluminium enclosure or support frame on a roof or tower has to be bonded into the copper equipotential conductor. The bolted joint sees thermal cycles and moisture.
How CUPAL solves it. A CUPAL washer in the bolted joint, with an outer diameter that covers the lug palm, or a plate cut to drawing where the contact face is larger.
Aluminium PV mounting rail → copper earth conductor
The problem you need to solve. Aluminium mounting rails, a copper earth conductor and steel fixings on the same roof.
How CUPAL solves it. Where the earth conductor is bolted to the aluminium rail, a CUPAL washer goes under the lug. The earthing point of the module frame is set by the module maker's installation manual; follow it.
Aluminium mast or pole → copper earth
The problem you need to solve. An antenna, signal or boat mast in aluminium, with a copper earth or lightning conductor.
How CUPAL solves it. The same joint as on the façade. The marine and mast version is covered on the marine page.
Questions from LPS designers and installers
Recommended CUPAL products
Applicable standards for this field
Knowledge base: CUPAL technical articles
4/10/2026
CUPAL bimetal installation and processing guide
Fitting a CUPAL bimetal washer step by step: surface prep, which face goes where, torque and edge protection outdoors. Plus the 260 °C / 4 h processing limit.
Read the full article →3/1/2026
Can copper and aluminium touch? Galvanic corrosion
They can touch, but where moisture reaches the joint the aluminium corrodes: 0.55 V apart in practice. What fails, and the bimetal washer that stops it.
Read the full article →2/15/2026
What is CUPAL? The copper-aluminium (Cu-Al) bimetal, explained
CUPAL is copper roll-bonded onto aluminium, 70/30 by layer thickness: one copper face, one aluminium face, for bolted copper-to-aluminium joints. 4.6 g/cm³, 41.9 MS/m.
Read the full article →