Applications
Copper-aluminium joints by industry
Wherever an aluminium conductor is bolted to a copper one, a CUPAL® washer, strip, cut plate or bimetal cable lug keeps the two metals apart. Find your joint below.
Where copper meets aluminium
Every electrical installation has a handful of points where an aluminium conductor is bolted to a copper one: the aluminium terminal of a transformer and the copper busbar, the aluminium feeder and the copper bar in a switchgear cabinet, a lightning-protection down-conductor and the earth termination, a copper earth cable and an aluminium mast. These joints fail more often than the rest of the installation, and usually not because they were badly tightened: an insulating oxide grows on the aluminium, and once moisture is present the two metals form a galvanic cell.
CUPAL is roll-bonded copper-aluminium bimetal: in the joint its aluminium face lies against aluminium and its copper face against copper. Which form you need depends on the joint:
| Your joint | Page | Part |
|---|---|---|
| Aluminium busbar to copper busbar | Busbars | CUPAL plate cut to the hole pattern |
| Aluminium feeder on a copper busbar in the cabinet | Switchgear | CUPAL washer M6–M20 |
| Aluminium cable on a copper terminal, free or already lugged | Cable lugs | Bimetal cable lug or washer |
| Aluminium terminal of a dry-type transformer, copper lug or bar | Transformer terminals | Plate cut to drawing or washer |
| Aluminium down-conductor on a copper earth conductor | Lightning protection | CUPAL strip 500 × 40 × 0.5 mm |
| Copper cable on an aluminium mast | Marine and masts | Washer or cut plate |
| Aluminium cell pole, PV mounting rail, charger cabinet | Solar, storage and charging | Washer, lug or cut tab |
Busbars
An aluminium busbar and a copper busbar in one bolted joint. A bimetal transition plate, washer or strip, cut to the existing hole pattern, keeps aluminium against aluminium and copper against copper.
Switchgear and distribution boards
Where an aluminium feeder lands on a copper busbar. An M6–M20 CUPAL washer, a bimetal cable lug or a transition plate cut to the existing hole pattern, with an EN 10204 2.2 test report on every shipment and 3.1 on request.
Cable lugs and connectors
A bimetal cable lug when the aluminium cable end is still free. A CUPAL washer when a lug is already fitted and the Al/Cu interface would sit under the bolt. A cut plate when the lug palm is wider than any washer.
Transformer terminals
The low-voltage terminals of cast-resin (dry-type) transformers are often aluminium. Between a copper lug or copper busbar and an aluminium terminal goes a bimetal plate or washer, as the transformer makers' installation instructions require.
Lightning protection
CUPAL strip 500 × 40 × 0.5 mm (the same format as DEHN 562 440) or an M6–M20 washer under an EN 62561-1 tested clamp, where an aluminium down-conductor meets a copper earth conductor. Supplied with an EN 10204 material certificate.
Marine bonding and masts
Copper bonding, earthing or lightning cable on an aluminium mast, mast step or busbar, from AWG
Solar, storage and charging
Aluminium cable on a copper terminal, an aluminium cell pole under a copper lug, an aluminium mounting rail on a copper earth conductor. Where a bimetal transition is needed, and where an aluminium or nickel-plated busbar is the better answer.
Frequently asked questions
Can't find your joint?
Tell us which metals meet, the bolt size and the cross-section, and within 24 hours we tell you which part you need.