Applications

Copper-aluminium joints by industry

Wherever an aluminium conductor is bolted to a copper one, a CUPAL® washer, strip, cut plate or bimetal cable lug keeps the two metals apart. Find your joint below.

Where copper meets aluminium

Every electrical installation has a handful of points where an aluminium conductor is bolted to a copper one: the aluminium terminal of a transformer and the copper busbar, the aluminium feeder and the copper bar in a switchgear cabinet, a lightning-protection down-conductor and the earth termination, a copper earth cable and an aluminium mast. These joints fail more often than the rest of the installation, and usually not because they were badly tightened: an insulating oxide grows on the aluminium, and once moisture is present the two metals form a galvanic cell.

CUPAL is roll-bonded copper-aluminium bimetal: in the joint its aluminium face lies against aluminium and its copper face against copper. Which form you need depends on the joint:

Your jointPagePart
Aluminium busbar to copper busbarBusbarsCUPAL plate cut to the hole pattern
Aluminium feeder on a copper busbar in the cabinetSwitchgearCUPAL washer M6–M20
Aluminium cable on a copper terminal, free or already luggedCable lugsBimetal cable lug or washer
Aluminium terminal of a dry-type transformer, copper lug or barTransformer terminalsPlate cut to drawing or washer
Aluminium down-conductor on a copper earth conductorLightning protectionCUPAL strip 500 × 40 × 0.5 mm
Copper cable on an aluminium mastMarine and mastsWasher or cut plate
Aluminium cell pole, PV mounting rail, charger cabinetSolar, storage and chargingWasher, lug or cut tab

Busbars

An aluminium busbar and a copper busbar in one bolted joint. A bimetal transition plate, washer or strip, cut to the existing hole pattern, keeps aluminium against aluminium and copper against copper.

IEC 61439-1IEC 61439-6
View details

Switchgear and distribution boards

Where an aluminium feeder lands on a copper busbar. An M6–M20 CUPAL washer, a bimetal cable lug or a transition plate cut to the existing hole pattern, with an EN 10204 2.2 test report on every shipment and 3.1 on request.

IEC 61439-1IEC 61439-2
View details

Cable lugs and connectors

A bimetal cable lug when the aluminium cable end is still free. A CUPAL washer when a lug is already fitted and the Al/Cu interface would sit under the bolt. A cut plate when the lug palm is wider than any washer.

IEC 61238-1-1IEC 61238-1-3
View details

Transformer terminals

The low-voltage terminals of cast-resin (dry-type) transformers are often aluminium. Between a copper lug or copper busbar and an aluminium terminal goes a bimetal plate or washer, as the transformer makers' installation instructions require.

IEC 60076-11IEC 61439-1
View details

Lightning protection

CUPAL strip 500 × 40 × 0.5 mm (the same format as DEHN 562 440) or an M6–M20 washer under an EN 62561-1 tested clamp, where an aluminium down-conductor meets a copper earth conductor. Supplied with an EN 10204 material certificate.

EN 62305-3EN 62561-1
View details

Marine bonding and masts

Copper bonding, earthing or lightning cable on an aluminium mast, mast step or busbar, from AWG

ABYC E-11ABYC TE-4
View details

Solar, storage and charging

Aluminium cable on a copper terminal, an aluminium cell pole under a copper lug, an aluminium mounting rail on a copper earth conductor. Where a bimetal transition is needed, and where an aluminium or nickel-plated busbar is the better answer.

IEC 60364-7-712IEC 61439-1
View details

Frequently asked questions

When aluminium and copper touch in a bolted joint and the joint can get damp, or carries high current and stays closed for years. In a dry, closed indoor enclosure the risk of galvanic corrosion is low, but the aluminium oxide film still degrades the joint. Outdoors, or in humid or salty air, protect the cut edge of the bimetal part as well.
One bolt and a finished lug: a washer, M6–M20. A narrow or bent transition, a lightning-protection run: strip, 500 × 40 × 0.5 mm from stock. Bar on bar, a transformer terminal, a mast step: a plate cut to drawing. Aluminium cable with a free end: a bimetal cable lug, 10–625 mm².
The drawing (DXF, PDF or JPG) or the dimensions: outline, thickness, hole pattern, quantity. For washers, the bolt size and the lug cross-section. We reply within 24 hours.
Stock washers, strip, bimetal lugs and 0.5 or 1.0 mm sheet: 2–10 working days from order to delivery. Custom cutting and made-to-order gauges: 5–10 working days in production. Custom orders, EU door to door: 2–4 weeks. Quotes within 24 hours.

Can't find your joint?

Tell us which metals meet, the bolt size and the cross-section, and within 24 hours we tell you which part you need.