Al down-conductor · Cu earthing · EN 62305

Lightning protection: aluminium down-conductor to copper earth

CUPAL strip 500 × 40 × 0.5 mm (the same format as DEHN 562 440) or an M6–M20 washer under an EN 62561-1 tested clamp, where an aluminium down-conductor meets a copper earth conductor. Supplied with an EN 10204 material certificate.

Where the aluminium down-conductor meets the copper earth

A lightning protection system often combines several metals: copper or steel earth electrodes in the ground, aluminium down-conductors on the façade, galvanised or stainless steel fixings on the structure. Where aluminium touches copper directly and the joint gets rain or condensation, the two metals form a galvanic cell and the aluminium side corrodes. The galvanic corrosion guide explains where the potential difference comes from and how to prevent it.

Meanwhile the joint keeps looking sound. The corrosion product, aluminium oxide, is a poor conductor: the clamp is tight, yet the resistance of the earth path rises. The periodic inspection measurement shows it, and so do the stains on the façade. That is why DEHN, among others, sells an Al/Cu Cupal strip for exactly these points.

In short

Where an aluminium down-conductor joins a copper earth conductor, the two metals should not touch. A CUPAL® bimetal strip or washer in the clamp puts its aluminium face to the down-conductor and its copper face to the earth. The clamp stays an EN 62561-1 tested component; CUPAL ships with an EN 10204 material certificate.

500 × 40 × 0.5mm
Stock strip, the DEHN 562 440 format
40–150mm
Custom strip width
M6–M20
Washers, 11 sizes from stock
24h
Quote

CUPAL under the tested clamp

CUPAL is cold roll-bonded copper-aluminium bimetal: aluminium on one face, copper on the other, the two layers bonded at the mill. In the joint, the aluminium face of the strip or washer lies against the down-conductor and the copper face against the earth conductor or earth mesh. Like metal meets like metal on both contact faces, so no bare Al/Cu interface remains in the clamp.

Keep the roles apart. EN 62561-1 sets the requirements and tests for lightning protection connection components (connectors, clamps, bonding and bridging components, expansion pieces and test joints); EN 62561-2 does the same for conductors and earth electrodes. The clamp manufacturer runs those tests on its own product. CUPAL strip or washer is not an LPS component; it is an interlayer material under the tested clamp, supplied with an EN 10204 2.2 test report, or a 3.1 inspection certificate on request. The system is still designed by the LPS designer to EN 62305-3.

Stock CUPAL strip is 500 × 40 × 0.5 mm, the same format as the DEHN 562 440 Cupal sheet strip. Wider strip comes in custom widths (40–150 mm) and thicknesses (0.5–2.0 mm), 5–10 working days in production. A joint held by one bolt takes a CUPAL washer, M6–M20. A special shape, such as a pad that fits under a particular clamp, is cut from your drawing.

Outdoors, the cut edge needs attention: on a strip or washer the Al/Cu bond line is exposed there. Put the joint in a protected position or cover the edge, and if the site is salty or very wet, say so in your enquiry. The same joint on boats and masts: copper bonding cable on an aluminium mast.

Replacing DEHN Cupal sheet

Matched by dimensions, not the same make. The DEHN data comes from the DEHN product data sheet and online store.

DEHN part562 440 CUPAB 500X40X0.5 AL CU
DEHN size500 × 40 × 0.5 mm
Our partCUPAL strip in the same format
AvailabilityFrom stock, 2–10 working days
DEHN part562 460 CUPAB 500X60X0.5 AL CU
DEHN size500 × 60 × 0.5 mm
Our partCUPAL strip in a custom width (40–150 mm)
AvailabilityProduction 5–10 working days
DEHN partCupal sleeve (CUPAH, e.g. 562 035, 562 050)
DEHN sizeSleeve pushed onto 25–50 mm² conductors
Our partWe do not supply sleeves; a washer or cut strip goes into the joint
AvailabilityMost DEHN sleeve variants are marked discontinued in the DEHN store

Typical Al/Cu points in lightning protection

Four places where aluminium meets copper on the lightning path.

01 / 04

Aluminium down-conductor → copper earth conductor at the test joint

The problem you need to solve. The aluminium down-conductor on the façade joins a copper earth conductor at the test joint or where it enters the ground. The joint is outside and gets rain and condensation.

How CUPAL solves it. CUPAL strip or washer under the tested clamp, aluminium face towards the down-conductor. Keep the clamp and the joint protected and the edge of the strip covered.

02 / 04

Aluminium equipment enclosure or support frame → copper equipotential bonding

The problem you need to solve. An aluminium enclosure or support frame on a roof or tower has to be bonded into the copper equipotential conductor. The bolted joint sees thermal cycles and moisture.

How CUPAL solves it. A CUPAL washer in the bolted joint, with an outer diameter that covers the lug palm, or a plate cut to drawing where the contact face is larger.

03 / 04

Aluminium PV mounting rail → copper earth conductor

The problem you need to solve. Aluminium mounting rails, a copper earth conductor and steel fixings on the same roof.

How CUPAL solves it. Where the earth conductor is bolted to the aluminium rail, a CUPAL washer goes under the lug. The earthing point of the module frame is set by the module maker's installation manual; follow it.

04 / 04

Aluminium mast or pole → copper earth

The problem you need to solve. An antenna, signal or boat mast in aluminium, with a copper earth or lightning conductor.

How CUPAL solves it. The same joint as on the façade. The marine and mast version is covered on the marine page.

Questions from LPS designers and installers

EN 62561 is the standard series for lightning protection system components. Part 1 covers connection components: the requirements and tests for connectors, clamps, bonding and bridging components, expansion pieces and test joints. Part 2 covers conductors and earth electrodes. The component manufacturer runs the tests; CUPAL strip or washer is an interlayer under the clamp and ships with an EN 10204 material certificate.
EN 62305 governs the design of the lightning protection system: risk assessment, protection level, routing, materials and cross-sections. EN 62561 governs the testing of individual components such as clamps and conductors. The designer is responsible at system level, the clamp manufacturer at component level.
Our stock CUPAL strip is made in the same format: 500 × 40 × 0.5 mm, with an aluminium and a copper layer. This is a match by dimensions, not the same make. If the specification names the DEHN part explicitly, agree the substitution with the designer. Instead of the 60 mm wide DEHN 562 460 we supply a custom width.
A Cupal sleeve is an Al/Cu tube pushed onto the end of a conductor; DEHN offered it for 25–50 mm² conductors, and most variants are marked discontinued in the DEHN store. CUPAL strip is a flat strip that goes under the clamp or between two flat conductors. We do not supply sleeves.
From stock, 500 × 40 × 0.5 mm. Custom widths from 40 to 150 mm and thicknesses from 0.5 to 2.0 mm, production 5–10 working days. Send the width, thickness and quantity; a rectangular strip needs no drawing, a custom outline needs a DXF, PDF or JPG drawing.
Yes, if the cut edge is protected. Like metals meet on the contact faces, but at the cut edge the Al/Cu bond line is exposed, and with moisture present the galvanic cell forms again there. On an outdoor joint cover the edge and put the clamp in a protected position. For salty or very wet sites, tell us the location and we will answer for that joint.
Stock strip and washers arrive 2–10 working days after the order. For custom widths and cut shapes we quote within 24 hours; production is 5–10 working days, and EU door to door is 2–4 weeks.

Applicable standards for this field

EN 62305-3
EN 62561-1
EN 62561-2

Ask an engineer

Application not listed? Describe it and we will advise.