Cable termination · Bolted joints · Al/Cu transition

Aluminium cable on a copper terminal: bimetal lug or CUPAL washer?

A bimetal cable lug when the aluminium cable end is still free. A CUPAL washer when a lug is already fitted and the Al/Cu interface would sit under the bolt. A cut plate when the lug palm is wider than any washer.

In short

An aluminium cable lands on a copper terminal in one of three ways. Free cable end: a bimetal cable lug, aluminium barrel on the cable, copper palm on the bar. Aluminium lug already fitted, or a copper lug on an aluminium bar: a CUPAL® washer under the bolt. Palm wider than any washer: a plate cut to drawing.

10–625mm²
Bimetal cable lugs, 109 part numbers
M6–M20
CUPAL washers, 11 sizes
1–2mm
Washer thickness, by size
24h
Quote for custom geometry

Aluminium cable, copper terminal: where the joint goes wrong

In a distribution board, an MCC, a substation or at an inverter the situation is the same: an aluminium cable arrives at a copper busbar, a copper breaker terminal or a copper stud, and a bolted joint at the cable end carries the current. If the aluminium touches the copper directly, two things start. An insulating oxide film grows on the aluminium, and wherever moisture is present the two metals form a galvanic cell. Meanwhile the different thermal expansion of the two metals works the joint on every load cycle, bolt preload drops, contact resistance rises and the joint runs warm.

Antioxidant compound slows this down, but the dissimilar pair stays in place and the joint needs regular checking. The lasting fix is to keep aluminium and copper from meeting under the bolt and let them meet inside a factory-bonded bimetal part instead. That part can be the cable lug itself, or a washer under the lug. The two are not equivalent, and they are not for the same job.

Which part goes into the joint?

The state of the cable end and the terminal material decide. Start from the first column.

SituationAluminium cable, end still free, going to a copper bar or terminal
PartBimetal cable lug (ICALCU), 10–625 mm², M8–M20
WhyThe Al/Cu transition sits in the body of the lug; copper meets copper under the bolt. One contact face.
AvailabilityFrom stock, 2–10 working days
SituationThe cable already has an aluminium lug and must bolt to a copper bar
PartCUPAL washer, M6–M20, 1–2 mm
WhyAluminium face to the lug, copper face to the bar. The existing termination stays.
AvailabilityFrom stock, 2–10 working days
SituationCopper lug on an aluminium bar or aluminium terminal
PartCUPAL washer, fitted the other way up
WhyCopper face to the lug, aluminium face to the bar. Same part number.
AvailabilityFrom stock, 2–10 working days
SituationLug palm wider than any washer, or several lugs on one bar
PartCUPAL plate cut to drawing
WhyCovers the whole palm, cut to the existing hole pattern.
AvailabilityQuote within 24 h, production 5–10 working days

Bimetal lug or washer? How to decide

On a new termination with aluminium cable, the bimetal cable lug is the first choice. You crimp the aluminium barrel onto the cable and bolt the copper palm to the bar. The transition is made at the factory inside the lug body, so copper meets copper under the bolt and only one contact face remains in the joint. The ICALCU range runs from 10 to 625 mm² and M8 to M20, as tubular lugs, inline connectors and pin lugs, with 109 part numbers in stock.

The CUPAL washer is the right part where the lug is already decided. In a retrofit the cable carries an aluminium lug and you do not want to cut it off. A copper lug has to go on an aluminium bar or terminal. The equipment terminal will not take a bimetal lug. In these cases the washer goes between lug and bar, aluminium face towards aluminium, copper face towards copper. The table on the switchgear page gives the size by bolt and lug cross-section.

A cut plate is needed when the lug palm is wider than the largest washer (Ø46 mm), or when several lugs sit on one stretch of bar. We then supply CUPAL sheet cut to your drawing and the existing hole pattern. Square or rectangular transition plates are also on CUPAL bimetal plates.

One thing to avoid: do not crimp a copper lug onto aluminium cable. The Al/Cu contact then sits inside the crimp, and no washer can fix that. Connecting copper to aluminium covers what to do at cable joints and cable ends.

Does the washer add contact resistance?

Yes, and it is better to say so plainly. The cable-lug maker ERGOM has published a measurement on a 120 mm² aluminium conductor carrying about 302–303 A. An aluminium lug with an Al-Cu washer on a copper bar measured 13.4–18.1 µΩ transition resistance and a steady-state temperature of 46.7–50.3 °C. ERGOM's own friction-welded KMA bimetal lug measured 1.9–2.1 µΩ and 36.1–37.1 °C. Their conclusion: the washer raises the resistance of the connection, and with it the temperature rise of the lug.

It is one manufacturer's own test. It gives no sample count and no test standard, and it did not test our washer. The direction makes physical sense, though: with an aluminium lug and a washer there is one contact face between lug and washer and a second between washer and bar, while a bimetal lug has only one. Our recommendation follows from that:

SituationRecommended part
New termination, aluminium cable, free cable endBimetal cable lug
Existing aluminium lug on a copper bar, retrofitCUPAL washer
Copper lug on an aluminium bar or terminalCUPAL washer, the other way up
Wide palm, several lugs, custom hole patternCut CUPAL plate

If a washer goes into the joint, three things keep its resistance low. The outer diameter should cover the whole lug palm, not just the area round the bolt; if the palm is wider, step up to a larger outer diameter. The contact faces should be clean and free of oxide. Torque comes from the lug or equipment manufacturer. We do not publish resistance figures of our own, because we have no such measurement.

Typical Al/Cu cable-end joints

Three common points, and which part belongs in each.

01 / 03

Aluminium cable (overhead or underground) → copper bar in a service cabinet

The problem you need to solve. The cabinet is outdoors or semi-outdoors, so the joint can get damp. The cable is aluminium, the bar copper, and nobody opens the joint for years.

How CUPAL solves it. On a new termination, a bimetal cable lug. On an existing aluminium lug, a CUPAL washer, but only in a dry, closed cabinet; in a damp location the bond line exposed at the cut edge of the washer makes the bimetal lug the better choice. If in doubt, describe the environment to us.

02 / 03

LV or MV aluminium cable → copper busbar in switchgear

The problem you need to solve. A large aluminium cable lands on the copper bar of the cabinet. If the cable end is still free, this is the moment that decides which part goes into the joint.

How CUPAL solves it. A bimetal cable lug on the cable, copper palm on the bar. If the cable already carries an aluminium lug, a CUPAL washer between lug and bar, with an outer diameter that suits the lug cross-section.

03 / 03

PV and BESS DC cabling → copper disconnector or fuse base

The problem you need to solve. The aluminium DC cable from the inverter or the storage system lands on copper terminals. The joint sees a daily thermal cycle.

How CUPAL solves it. The same decision as above. The other Al/Cu points in solar and battery systems are covered on the renewable-energy page.

Questions from installers

The bolt size gives the thread, the conductor cross-section of the lug gives the outer diameter. For example, an M12 bolt with a 300 mm² lug needs the M12 (large), Ø30 mm washer (ICALCU12CS), because the plain M12 (Ø26 mm) only goes to 240 mm². If the palm is wider than the washer you picked, step up to the next outer diameter. The full table is on the switchgear page and on the washer product page.
We do not recommend it. In the crimp the aluminium strands touch the copper barrel directly, and a washer cannot fix that point because it sits under the bolt, not in the crimp. Crimp an aluminium or bimetal lug onto aluminium cable; if the terminal is copper, a bimetal lug makes the transition in one step.
Not for the transition: each face meets its own metal. The CUPAL installation guide asks for clean, oxide-free contact faces with no oil or general-purpose grease on them; if you use a contact compound for extra moisture protection, use one made for aluminium joints. When crimping an aluminium or bimetal lug, follow the lug manufacturer's instructions.
We match by bolt size and outer diameter. The Klauke CS1635 is an M16 disc with a 17 mm inner and 35 mm outer diameter; our M16 ICALCU16CS also has a 35 mm outer diameter. For the NEXANS Cupal M 12 Al-Cu, the ICALCU12CS2 or ICALCU12CS fits, depending on the lug cross-section. The match is by dimensions, not the same make; compare the outer diameter with the lug palm before you order.
Yes, if the joint is protected. At the cut edge of the washer the Al/Cu bond line is exposed, and with moisture present the galvanic cell forms again there. Klauke lists its own Cupal disc for dry environments, and for humid environments with tinned aluminium lugs. For an outdoor or humid joint, either choose a bimetal lug, or keep the joint in a closed, protected place and cover the edge. If you are unsure, describe the environment and we will answer for that specific joint.
IEC 61238-1-1 (up to 1 kV) and IEC 61238-1-3 (above 1 kV) are type tests for compression and mechanical connectors, that is lugs and splices. The lug manufacturer tests its own product; the test does not apply to a washer. The CUPAL washer ships with a material certificate (EN 10204 2.2 test report, 3.1 inspection certificate on request), not with a connector type-test certificate.
Washers and bimetal lugs are stock items: 2–10 working days from order to delivery. For plates cut to drawing we quote within 24 hours; production is 5–10 working days, and EU door to door is 2–4 weeks.

Applicable standards for this field

IEC 61238-1-1
IEC 61238-1-3
IEC 60228

Ask an engineer

Application not listed? Describe it and we will advise.