GuidesSeptember 8, 202622 min read

Connecting copper to aluminium: which part for which joint

Connecting copper to aluminium is not one job but five, and each takes a different part: a crimped bimetal lug where an aluminium cable lands on a copper terminal, an inline connector where an aluminium conductor meets a copper one end to end, a bimetal washer or a cut plate where a copper lug bolts onto an aluminium busbar, and the same washer turned over where an aluminium lug bolts onto a copper busbar. For solid domestic wiring below 10 mm², nothing we supply fits at all. This page sends you to the right part in the right size, or tells you plainly that we are not your supplier.

In short

Copper and aluminium corrode wherever they are bolted or clamped together in the presence of moisture, and a copper-aluminium bimetal transition is the permanent fix. Which part you need depends on which of the five joints you are making. Both bolted cases, copper lug on an aluminium bar and aluminium lug on a copper bar, take the same washer; only its orientation changes. For solid domestic wiring below 10 mm² we have no product for you.

5
Joint types
10mm²
Smallest bimetal lug
M6–M20
Bimetallic washer sizes in stock

Which joint are you actually making?

Two things decide the part: which side is aluminium, and how the two conductors physically meet. The cross-section decides whether we can help at all.

The jointWhat it looks likeThe partCross-section
Solid aluminium house wiring1.5–4 mm² solid aluminium in a flat, often a sealed meter tailNone of ours; see the next sectionBelow our range
Aluminium cable onto a copper terminalCable end at a busbar, breaker or terminal blockBimetal tubular lug, or a pin lug where the device takes a pinTubular lug 10–625 mm² · pin lug Al 16–300 mm² (Ø6–Ø18 mm pin)
Aluminium conductor to copper conductor, in lineTwo cable ends joined end to end, no bolt anywhereAl/Cu inline connectorAl 16–500 mm² × Cu 10–400 mm²
Copper lug bolted to an aluminium busbar or structureCopper lug palm, bolt, aluminium bar or mast fittingBimetal washer M6–M20, copper face to the lug, or a cut plateSet by the bolt, not the cable
Aluminium lug bolted to a copper busbar or terminalAluminium lug palm already crimped, bolt, copper bar or terminal padThe same bimetal washer, turned over: aluminium face to the lug, no new lug needed. Which way round →Set by the bolt, not the cable

For the bolted cases, if you are weighing a new bimetal lug against a CUPAL® washer under the existing copper lug, see bimetal lug or CUPAL washer: which one the joint needs. What the material is and how it is made is covered in What is CUPAL?

Solid aluminium house wiring, 1.5–4 mm²: we are not your supplier

If the aluminium in front of you is 1.5, 2.5 or 4 mm² solid conductor in a domestic installation (the original aluminium wiring in an older flat, or a sealed meter tail you are not permitted to replace), nothing in our range fits it. Our smallest bimetal cable lug is 10 mm², and inline connectors start at 16 mm² on the aluminium side. There is no smaller version and no exception to ask us about.

At that size the correct answers are the ordinary ones: a clamp terminal approved for aluminium conductors, used with an oxide-inhibiting contact paste, or replacing the aluminium run with copper. Both are sound engineering there, and neither is a product we supply. In practice that means:

  • An approved clamp terminal with its maker's paste. WAGO, for example, approves its 2273, 222 and 224 series and its 279–281 and 780–781 rail-mounted terminals for solid aluminium conductors up to 4 mm², used with its Alu-Plus contact paste (249-130), and derates them to 16 A at 2.5 mm² and 22 A at 4 mm². Its common 221 lever connector is not approved for aluminium.
  • Insulated Al-Cu connectors, sold for exactly this joint by electrical wholesalers.
  • An electrician. Where the aluminium run feeds a sealed meter position or you cannot see the whole circuit, have it done by someone who can.

Aluminium conductor onto a copper terminal: bimetal cable lug

The commonest industrial version of the problem: an aluminium cable terminating on a copper busbar, breaker or terminal block. A bimetal lug puts the transition inside the part: the aluminium barrel is crimped onto the cable, the copper palm bolts to the copper terminal, and no dissimilar pair is exposed.

The tubular lug covers 10–625 mm² with bolt holes from M8 to M20, palm dimensions to DIN 46329, in 52 stocked SKUs. The cheapest is ICALCU108 at 10 mm²/M8, HUF 1,981 net. A worked example from the middle of the range: a 240 mm² aluminium cable landing on an M16 stud is ICALCU24016, HUF 7,194 net. The SKU reads as cross-section then bolt size, so the part number is a lookup once you know those two numbers.

Where the device takes a copper pin rather than a bolt, as on isolators and some circuit breakers, the pin lug covers aluminium 16–300 mm² with pin diameters Ø6 to Ø18 mm, 11 SKUs, from ICALCU16B6V at HUF 4,926 net to ICALCU300B18V at HUF 16,939 net.

Lug and connector prices on this page are net list, effective 20 July 2026; gross is net × 1.27. The cable-lug product page carries the current figures.

There is a second route to the same joint. Where an aluminium cable lands on a copper terminal, it is often faster and cheaper to crimp the plain aluminium lug your wholesaler already stocks and fit a copper-aluminium washer cut to that lug's palm than to source a bimetal lug in your exact geometry. That is the cut-to-size route, and it is covered further down this page.

That route adds a second contact interface, and lug makers measure the cost of it. ERGOM, a Polish lug maker, terminated a 120 mm² aluminium cable at about 300 A on a copper busbar both ways in its factory laboratory: its aluminium lug with a standard Al-Cu washer measured 13–18 µΩ between palm and bar and ran at 47–50 °C, its bimetal lug about 2 µΩ and 36–37 °C. It is a maker's test of its own product, and it does not state the washer, the surface preparation or the torque, but the direction is what you would expect from two contact interfaces in place of one. On a new termination that carries its rated current continuously, the bimetal lug is the better joint. The washer route suits lugs that are already crimped, geometries no lug fits, and earthing or bonding joints that carry little current.

One thing to check before you order: a bimetal lug is only the answer while the cable end is still open. If the cable is already terminated and only the bolted interface is dissimilar, the washer is the answer, whichever way round the metals sit: a plain copper lug on an aluminium bar, or a plain aluminium lug on a copper bar. Both bolted cases are covered below.

Aluminium conductor to copper conductor, end to end: Al/Cu inline connector

Sometimes there is no terminal at all: an aluminium conductor is joined end-to-end with a copper one, on an overhead-line repair or where an aluminium run is extended in copper. That is the Al/Cu inline connector: a bimetal sleeve crimped onto the aluminium at one end and the copper at the other, with the transition sealed inside.

It is specified by the two conductor cross-sections and nothing else: aluminium 16–500 mm² against copper 10–400 mm², 46 stocked SKUs, from ICALCU1610V (Al 16 / Cu 10) at HUF 2,711 net up to ICALCU500400V (Al 500 / Cu 400) at HUF 43,588 net. There is no bolt size on an inline connector; if you are looking for one, you are in the wrong row of the table at the top of this page.

Copper lug bolted to an aluminium busbar: bimetal washer or cut plate

A copper cable lug bolted flat onto an aluminium busbar, an aluminium enclosure, an earthing bar or a mast fitting. With nothing between them, the aluminium corrodes under the palm. The washer solves it by one rule, which is worth stating before the sizes because it also settles the mirror case in the next section: each face of the washer meets its own metal. The copper face meets copper, the aluminium face meets aluminium, and the Cu-Al interface itself is sealed inside the disc where no electrolyte reaches it. In this joint that means the copper face against the copper lug palm and the aluminium face against the aluminium bar. CUPAL prescribes no torque of its own; tighten to the figure the bolt and the equipment call for.

A note on names. Drawings that call for a "transition washer" sometimes mean a profiled copper-alloy washer, whose raised pattern bites through the aluminium oxide film as the bolt is tightened. That part is copper alloy throughout, and the transition is made at assembly. What follows is a roll-bonded bimetal, where the transition is built into the material. If your drawing does not say which, how to tell the two apart settles it in a few seconds.

Bolt sizeOuter dia.Max. lug cross-sectionSKU
M616 mm120 mm²ICALCU6CS
M818 mm120 mm²ICALCU8CS
M1023 mm240 mm²ICALCU10CS
M10 (large)26 mm300 mm²ICALCU10CS2
M1226 mm240 mm²ICALCU12CS2
M12 (large)30 mm400 mm²ICALCU12CS
M12 (extra)46 mm500 mm²ICALCU12CS3
M1635 mm500 mm²ICALCU16CS
M16 (large)46 mm630 mm²ICALCU16CS2
M2037 mm500 mm²ICALCU20CS
M20 (large)46 mm630 mm²ICALCU20CS2

The max. lug cross-section column is the largest lug palm that the outer diameter still covers fully. Thickness is 1–2 mm depending on the size, confirmed per part number in the quote. Lead time is 2–10 working days from order to delivery, and we quote small quantities too; order quantity and pack size are confirmed in the quote. Net list prices are on the product page: see net list prices for all 11 washer sizes, which also carries a cross-reference to the designations other distributors use. The size guide gives the bore diameter for each bolt size. If what you have is a distributor code rather than a size (880111, Cupal M 10 Al-Cu, ICALCU10CS), the part number cross-reference maps it onto a stocked size. For a copper cable on an aluminium mast or antenna pole, where salt spray makes the same joint fail far faster, see copper bonding to aluminium masts.

Two numbers decide it: the bolt and the lug palm

The bolt sets the bore: an M10 joint takes an M10 washer. The width of the lug palm sets the outer diameter, because the palm has to seat fully on the washer face rather than overhang it. If the palm is wider than the largest stock washer for your bolt, step up the diameter or have a plate cut to the actual footprint. A washer that covers only the area around the bolt leaves the dissimilar contact exposed where it matters most. Thickness is 1–2 mm depending on the size; we confirm it per part number in the quote, so you can allow for it in the bolt length. Surface preparation, orientation and inspection are set out step by step in the installation guide.

Aluminium lug bolted to a copper busbar: the same washer, turned over

The mirror of the case above, and just as common: the lug is aluminium and the bar is copper. An aluminium cable lug on a copper busbar, on a copper terminal or on a copper earth bar.

The part does not change, only its orientation. Because each face of the washer meets its own metal, the stack here runs aluminium lug, then the washer's aluminium face, then its copper face, then the copper bar — two like-metal contacts, with the Cu-Al interface sealed inside the disc exactly as before. The washer is not a handed part (there is no left and right, no top and bottom), but it does have an orientation: the only thing you decide is which face goes against which conductor. The same 11 stocked sizes, M6 to M20, serve this joint.

Check the faces before you fit it: the reddish face is copper, the light silver face is aluminium. On an oxidised part, light sanding settles it, and if sanding reveals no copper face at all, what you are holding is not a bimetal washer. Note that the installation guide sets out the copper-lug-on-aluminium-bar orientation; here the same steps apply with the faces reversed.

If the aluminium lug is already crimped, you do not need a bimetal cable lug here; buying one is the expensive way to get this wrong. A bimetal lug puts the transition inside the termination, which only helps you while the cable end is still open, and yours is not. The only dissimilar contact left is the one under the bolt, and that is what the washer removes. The alternative is cutting off a good lug and re-crimping to a bimetal one, which starts at HUF 1,981 net (ICALCU108) and reaches HUF 7,194 at the 240 mm²/M16 size, to fix a joint the washer fixes without touching the termination. The exception is a joint that runs close to its rated current all the time: there the lower contact resistance of a bimetal lug, shown in the ERGOM test above, can justify re-terminating.

We do not supply the aluminium lug itself. Our ICALCU lugs are bimetal only (an aluminium barrel with a copper palm or pin), so buy the plain aluminium lug wherever you normally buy lugs. What we supply is what goes between it and the bar.

Sizing is unchanged from the case above: the bolt sets the bore, and the aluminium lug's palm sets the outer diameter. Measure the palm rather than inferring it from the cable cross-section. If it overhangs the largest washer for your bolt, have a plate cut to the actual footprint.

When no stock size fits: a part cut to your DXF

Stock sizes are faster and cheaper as long as your joint fits them. When they do not (a lug palm that matches no standard washer, a busbar transition with its own hole pattern, a terminal plate to a given contour), we supply the part cut from board; the cutting is done by our processing partner.

Discs, strips, rectangles and arbitrary contours, in 0.5, 1.0, 1.5 and 2.0 mm, from a DXF, PDF or JPG drawing. Minimum is one 500 × 500 mm board of raw material, with board prices on the sheet product page; the per-piece price is that board plus cutting labour, set by shape complexity and quantity. Quote within 24 hours, production in 5–10 working days, and the EN 10204 certificate covers cut parts exactly as it covers stock sizes.

This is the route behind the plain-aluminium-lug option above: a washer cut to the palm you already have, rather than a bimetal lug sourced to your geometry. Where the transition has to be flexible or wrapped, as in lightning protection, CUPAL strip is the same material in band form. More on cutting to size and the sheet it comes from.

Paste, stainless washer, CCA: why none of them is the answer

Copper and aluminium in contact with an electrolyte form a galvanic cell. Aluminium is the less noble metal, so it corrodes, and the corrosion product is an insulating oxide: contact resistance rises, the joint heats, the heat accelerates the corrosion, and the joint loosens. How large the potential difference is, and what the published figures mean, is set out in galvanic corrosion prevention.

Contact paste keeps the electrolyte out for a while, but it does not remove the potential difference. It dries out, runs, or is squeezed from a joint that heats and moves, and then the joint needs opening, cleaning and fresh paste.

A stainless washer does not separate the metals at all. The austenitic A2 and A4 grades of stainless fasteners sit next to copper in the galvanic tables, so the washer keeps the same couple against the aluminium and adds a third metal to the joint.

Copper-clad aluminium (CCA) is a conductor, not a transition part. A thin copper skin covers an aluminium core, so the surface behaves like copper while weight and price stay close to aluminium, which is why CCA is used where conductor weight and cost matter. As a transition it is fragile: wherever a crimp, a clamp screw, a cut end or a scratch breaks the skin, the aluminium core meets copper inside the termination and corrodes locally. CUPAL is a different construction: a copper layer roll-bonded to an aluminium layer across the whole face, so each contact face of the part is solid copper or solid aluminium. Its bond line does reach the surface at a cut edge, which is why outdoor and damp joints need that edge protected or covered.

Five ways to make the copper-aluminium transition

What each one does about the galvanic couple, and what it costs you in maintenance.

MethodBimetal transition (washer, plate or lug)
PermanencePermanent, metallurgical bond
Galvanic protectionRemoved; copper to copper, aluminium to aluminium
MaintenanceRoutine bolted-joint checks only
MethodOxide-inhibiting paste
PermanenceTemporary, dries and squeezes out
Galvanic protectionDelays it, never removes it
MaintenanceRe-torque and renew
MethodStainless steel washer
PermanenceMechanical only
Galvanic protectionNone; austenitic stainless is as noble as copper against aluminium
MaintenanceOpen and clean periodically
MethodCopper-clad aluminium (CCA) conductor
PermanenceLasts while the copper skin is intact
Galvanic protectionLost wherever the skin is cut, crimped through or scratched
MaintenanceDepends on the condition of the skin
MethodBare bolted Cu-Al joint
PermanenceNo transition at all
Galvanic protectionNone; a direct galvanic couple
MaintenanceRe-torque, then replace

What the standards say, and what they do not

This is where specifications get written loosely. IEC 61238 for cable connectors and IEC 61439 for low-voltage switchgear set requirements on the installed joint: contact resistance, temperature rise, long-term stability. DIN 43671 (copper) and DIN 43670 (aluminium) rate the busbars themselves for continuous current. None of them are certifications of the CUPAL material, and nobody can hand you a certificate saying a washer is "IEC 61439 approved". What a bimetal transition does is make those requirements achievable, and keep them achievable over the equipment's life.

The paperwork you can name in a bill of materials: an EN 10204 2.2 material certificate with every delivery as standard, 3.1 on request, both covering custom-cut parts, because cutting does not affect the certification of the base material. The raw material comes from an ISO 9001:2015 certified supplier, and the grades carry Werkstoff numbers under DIN 17007 (aluminium 3.0255) and DIN 1787 (copper 2.0065). The EN 10204 article explains what separates a 2.2 from a 3.1.

The material data behind the washer, the cut plate and the strip is short: 70 % aluminium / 30 % copper by layer thickness, conductivity 41.9 m/(Ω·mm²), bond strength 70–110 N/cm. That ratio is worth checking against whatever else you are quoted, because most sellers publish no cladding ratio at all, which makes it impossible to specify against a drawing.

What to send us for a quote

  • Cross-section and bolt size. Cable cross-section in mm² and the bolt or stud the joint lands on. That is enough to name the lug, the connector or the washer.
  • The lug palm width, or a drawing. If the palm is wider than a stock washer, send a DXF, PDF or JPG, or a photograph with the bolt size, which is often enough to start.
  • Quantity, and the certificate you need. 2.2 as standard, 3.1 if your specification calls for it.

Send those three and the quote comes back within 24 hours on working days. Ask for a quote, or size a cut part in the configurator.


Not sure which of the five joints you have? Send us the dimensions and the priced quote comes back within 24 hours.

Frequently asked questions

Two numbers decide it. The bolt sets the bore (an M10 joint takes an M10 washer), and the width of the lug palm sets the outer diameter, because the palm must seat fully on the washer face. Stock outer diameters run 16, 18, 23, 26, 30, 35, 37 and 46 mm across M6 to M20, each listed with a maximum lug cross-section. If the palm is wider than the largest washer for your bolt, step up the diameter or have a plate cut to the footprint. Thickness is 1–2 mm depending on the size, confirmed per part number in the quote.
No. Solid aluminium house wiring runs 1.5, 2.5 and 4 mm², and our range does not reach it: the smallest bimetal cable lug is 10 mm² and inline connectors start at 16 mm² on the aluminium side. At that size the correct answer is a clamp terminal approved for aluminium, used with an oxide-inhibiting contact paste, or replacing the aluminium run with copper. Neither is something we sell, and there is no smaller version to ask us for.
It depends on whether the cable end is still open. If the aluminium cable is not yet terminated and it lands on a copper terminal, you need a bimetal lug: the aluminium barrel is crimped to the cable and the copper palm bolts to the terminal. It also gives the lower-resistance joint: in ERGOM's published test a bimetal lug measured about 2 µΩ against 13–18 µΩ for an aluminium lug with a washer. If the cable is already terminated and only the bolted interface is dissimilar, you need a bimetal washer between the palm and the bar, or a cut plate when the palm is wider than any stock washer. That holds both ways round: a copper lug on an aluminium busbar takes the washer copper face to the lug, and an aluminium lug on a copper busbar takes the same washer turned over, aluminium face to the lug. Re-terminating a sound aluminium lug onto a bimetal one only pays where the joint runs close to its rated current all the time.
No. Crimping a copper barrel onto aluminium strands puts the two metals in contact inside the crimp, where moisture can reach them and the aluminium corrodes. Use a bimetal lug, with an aluminium barrel for the cable and a copper palm for the terminal, or a plain aluminium lug with a bimetallic washer under the bolt where it meets copper.
Only with the series WAGO approves for aluminium and with its contact paste. WAGO approves its 2273, 222 and 224 series and its 279–281 and 780–781 rail-mounted terminals for solid aluminium conductors up to 4 mm², used with Alu-Plus contact paste (249-130), and derates them to 16 A at 2.5 mm² and 22 A at 4 mm². The common 221 lever connector is not approved for aluminium. We do not sell these; for domestic wiring, ask an electrician.
With an Al/Cu inline connector: a bimetal sleeve crimped onto the aluminium at one end and the copper at the other, so the transition is sealed inside the part. It is specified by the two conductor cross-sections only: aluminium 16–500 mm² against copper 10–400 mm², 46 stocked SKUs, from HUF 2,711 net. There is no bolt size on an inline connector.
Not on its own. Paste displaces moisture from the contact face and so delays corrosion, but it does not remove the potential difference between copper and aluminium. It dries out, runs, or is squeezed from a joint that heats and moves, and the joint then needs re-torquing and fresh paste. A bimetal transition removes the couple instead of postponing it. Once a bimetal washer is in the joint, paste is optional protection for the faces: our installation guide asks for clean, oxide-free contact faces, no oil or ordinary grease, and, if you want a compound, one made for aluminium joints.
Not per unit area. CUPAL conducts at about 41.9 m/(Ω·mm²), roughly 0.72 of copper, so a bimetal part needs around 1.41× the cross-section of a copper one for the same current. On a bolted transition that is usually irrelevant, because the contact area is set by the bolt and the lug palm rather than by ampacity, and on an earthing or bonding path it rarely applies at all. It does matter where the transition itself carries working current along its length.
Not reliably. CCA carries a thin copper skin over an aluminium core and is made as a conductor. Wherever a crimp, a clamp screw, a cut end or a scratch breaks that skin, the aluminium core meets copper inside the termination and corrodes locally. A CUPAL transition has a solid copper face and a solid aluminium face, roll-bonded across the whole area, so each contact is like-metal.
CUPAL is a roll-bonded copper-aluminium bimetal: a Cu-ETP copper layer on an EN AW-1050A aluminium layer, 70 % aluminium / 30 % copper by layer thickness, which is about 59 % copper by mass. Density is 4.6 g/cm³ and conductivity 41.9 m/(Ω·mm²). The copper-aluminium interface lies inside the material; only at a cut edge does the bond line reach the surface.
An EN 10204 2.2 material certificate accompanies every shipment as standard, and a 3.1 inspection certificate is available on request. Both cover custom-cut parts as well as stock sizes, because cutting does not affect the certification of the base material. The raw material comes from an ISO 9001:2015 certified supplier, and the grades carry Werkstoff numbers under DIN 17007 and DIN 1787.

Have a question?

Email us or use the form: we reply within 24 hours on working days.

Get a Quote