LV switchgear · Distribution boards · Panel builders

Aluminium cable on a copper busbar in the switchgear cabinet

Where an aluminium feeder lands on a copper busbar. An M6–M20 CUPAL washer, a bimetal cable lug or a transition plate cut to the existing hole pattern, with an EN 10204 2.2 test report on every shipment and 3.1 on request.

You are the one signing the routine verification

The IEC 61439 series splits the work in two. The original manufacturer brings the design verification with a certified system; the assembly manufacturer, the panel builder, puts the cabinet together, carries out the routine verification and signs it. The moment you depart from the certified configuration, the burden of proof moves with you.

There is one joint in that cabinet you cannot verify your way around: the incoming aluminium feeder landing on the copper busbar through a bolted joint. IEC 61439-1 sets a 70 K temperature-rise limit for terminals for external insulated conductors. A direct Al/Cu contact builds an oxide film and, wherever moisture reaches it, starts galvanic corrosion; within a few years the junction can show up as a hot spot on a thermal survey and drift out of that budget under peak load. Antioxidant compound can be re-applied every few years, but that means booking a maintenance window, documenting the work and signing for it.

The trouble does not appear at handover. It appears two or three years later, on a thermographic survey, as a hot spot on a document with your name on it.

In short

In a switchgear cabinet the incoming aluminium feeder meets the copper busbar. If a lug is already crimped on, an M6–M20 CUPAL® bimetal washer goes into the bolted joint, chosen by bolt size and lug cross-section. If the cable end is still free, a bimetal cable lug is the better part. Both ship with an EN 10204 2.2 test report.

M6–M20
11 CUPAL washer sizes
1–2mm
Washer thickness, by size
109
Bimetal cable lug part numbers from stock
24h
Quote for custom geometry

Which washer goes into the joint

Two numbers decide it: the bolt in the joint gives the thread size, and the conductor cross-section of the lug gives the outer diameter you need. Check the palm width separately; if it is wider than the outer diameter of the row you picked, step up to the next outer diameter. Net list prices per size are on the CUPAL washer product page.

Bolt sizeM6
Outer Ø16 mm
Max. lug cross-section120 mm²
SKUICALCU6CS
Bolt sizeM8
Outer Ø18 mm
Max. lug cross-section120 mm²
SKUICALCU8CS
Bolt sizeM10
Outer Ø23 mm
Max. lug cross-section240 mm²
SKUICALCU10CS
Bolt sizeM10 (large)
Outer Ø26 mm
Max. lug cross-section300 mm²
SKUICALCU10CS2
Bolt sizeM12
Outer Ø26 mm
Max. lug cross-section240 mm²
SKUICALCU12CS2
Bolt sizeM12 (large)
Outer Ø30 mm
Max. lug cross-section400 mm²
SKUICALCU12CS
Bolt sizeM12 (extra)
Outer Ø46 mm
Max. lug cross-section500 mm²
SKUICALCU12CS3
Bolt sizeM16
Outer Ø35 mm
Max. lug cross-section500 mm²
SKUICALCU16CS
Bolt sizeM16 (large)
Outer Ø46 mm
Max. lug cross-section630 mm²
SKUICALCU16CS2
Bolt sizeM20
Outer Ø37 mm
Max. lug cross-section500 mm²
SKUICALCU20CS
Bolt sizeM20 (large)
Outer Ø46 mm
Max. lug cross-section630 mm²
SKUICALCU20CS2

What CUPAL does in the joint

If the bill of materials or the earthing drawing calls for a transition washer between an aluminium bar and a copper lug, first check which part is meant. The same name is used for profiled copper-alloy washers that pierce the oxide film when tightened; that is a different principle and not a bimetal part. The bimetallic vs toothed transition washer comparison shows how to tell them apart. If the specification means a genuine copper-aluminium bimetal disc, pick the row from the table above by bolt size and lug cross-section.

CUPAL puts the whole transition into a single roll-bonded plate or washer, and the rule is the same everywhere: each face meets its own metal. An aluminium lug on a copper bar takes the washer with the aluminium face towards the lug; a copper lug on an aluminium bar takes the same washer the other way up. Either way, the driver of galvanic corrosion, two dissimilar metals sharing an electrolyte at the joint, is removed at the contact itself. No compound goes between the contact faces. Tightening torque remains whatever the busbar and bolt manufacturers specify; CUPAL has no torque table of its own, and the fitting sequence is in the CUPAL installation guide.

If the cable end is still free, a bimetal cable lug does the same job with one contact face fewer, so check that first on a new connection. The bimetal lug or CUPAL washer page sets out the decision.

Net list prices per size, quantity discounts and the distributor cross-reference (NEXANS, Mentavill) are on the CUPAL washer product page.

The base material carries DIN 17007 / DIN 1787 designations (aluminium AL 99.5 / 3.0255, copper E1-Cu58 / 2.0065). Every shipment comes with an EN 10204 2.2 test report; an EN 10204 3.1 inspection certificate is available on request. Our supplier is ISO 9001:2015 certified, and HIDRA-MIX Kft. has been operating in Budapest since 1991.

What this looks like in numbers

70K
Temperature-rise limit at terminals for external conductors (IEC 61439-1)
11
Washer sizes from M6 to M20, 1–2 mm thick
70–110N/cm
CUPAL Al-Cu bond strength
2–4weeks
Custom order, EU door to door including transit

Where it fits in the cabinet

Four places in the cabinet where you will meet an Al/Cu joint; the table above gives the SKU for each.

01 / 04

Incoming feeder → main busbar

The problem you need to solve. A three-phase aluminium feeder (e.g. 3×240 mm² Al) lands on the main copper busbar through a bolted lug. Thermally it is one of the hardest-worked joints in the cabinet.

How CUPAL solves it. If the cable is not yet terminated, a bimetal cable lug. If it already carries an aluminium lug, a CUPAL washer or a transition plate cut to the existing pattern between lug and bar, aluminium face to the lug. Torque follows the busbar and bolt manufacturers' specification.

02 / 04

Outgoing feeder: Cu busbar → Al cable to MCC

The problem you need to solve. The outgoing direction lands copper busbar on aluminium cable feeding a motor control centre or sub-distribution. Same Al/Cu bolted joint, often with stricter handover documentation.

How CUPAL solves it. A CUPAL washer between busbar and lug. One part, no extra tools, and the material ships with an EN 10204 certificate you can put in the panel dossier.

03 / 04

N / PE equipotential bar

The problem you need to solve. In a multi-storey riser, aluminium neutral and PE conductors terminate on the cabinet's copper bonding bar. Thermal cycling relaxes the bolted joint and the oxide adds resistance.

How CUPAL solves it. A CUPAL transition plate between bonding bar and riser. Both bolted faces put like metal against like metal, so the joint no longer depends on the aluminium oxide film.

04 / 04

Brownfield retrofit

The problem you need to solve. A 10–20-year-old cabinet gets an aluminium feeder upgrade, but the original copper busbar stays. Catalogue parts do not always fit the old bolt pattern or the stack-up height.

How CUPAL solves it. A CUPAL plate cut to the existing pattern from a DXF, PDF or JPG drawing. Quote within 24 hours, 5–10 working days in production, and it installs without structural modification.

Compared to the usual alternatives

Four familiar approaches to the same bolted joint, how they behave over time, and how much freedom you have on geometry.

ApproachCu lug + antioxidant compound on aluminium
Joint behaviour over timeAcceptable, drifts over time
MaintenancePeriodic inspection, re-tightening, new compound
GeometryStandard lug footprints
ApproachBimetal compression lug
Joint behaviour over timeStable; one contact face
MaintenanceTorque check after commissioning
GeometryFixed catalogue geometry; needs a free cable end
ApproachOver-sized pure copper conductor
Joint behaviour over timeNo Al/Cu joint
MaintenanceNone specific
GeometryRemoves the joint, but the conductor run is re-specified
ApproachCUPAL washer or custom-cut plate
Joint behaviour over timeLike-for-like faces; cut edge to protect in humid air
MaintenanceTorque check after commissioning
Geometry11 stocked washer sizes, or any outline from DXF, PDF or JPG

Washer, lug or cut plate

The same material in four forms. The geometry of the joint decides which one belongs in it.

FormCUPAL washer (M6–M20)
When this is the oneA finished lug bolts onto the bar and the bolt pattern is fixed
Geometry11 stocked sizes, 1–2 mm thick by size
AvailabilityFrom stock, 2–10 working days to delivery
FormCUPAL bimetal cable lug (ICALCU)
When this is the oneThe cable end itself has to change metal
Geometry109 SKUs; tubular lugs, inline connectors, pin lugs
AvailabilityFrom stock, 2–10 working days to delivery
FormCUPAL sheet, 500 × 500 mm
When this is the oneBar-to-bar transition, larger contact area
Geometry0.5 / 1.0 / 1.5 / 2.0 mm
Availability0.5 and 1.0 mm from stock; 1.5 and 2.0 mm 5–10 working days in production
FormCustom cutting
When this is the oneThe existing bolt pattern takes no catalogue part
GeometryAny outline from a DXF, PDF or JPG drawing
AvailabilityQuote within 24 h, 5–10 working days in production

What we supply, and what we don't

We supply into your bill of materials; we do not bid for your work. We do not build cabinets, and we do not sell enclosures, busbar systems, terminal blocks, circuit breakers or installation labour. One line item goes into your BOM: the copper-aluminium transition, as an M6–M20 washer, as an ICALCU bimetal cable lug, 109 SKUs from stock, as CUPAL sheet, 500 × 500 mm, or as an outline cut from your DXF, PDF or JPG drawing. Cutting and punching are done by a partner workshop.

We do not sign the declaration of conformity for the cabinet either. EN 10204 2.2, or 3.1 on request, certifies the material; IEC 61238 and IEC 61439 apply to the assembly the part is fitted into, not to CUPAL itself. Under IEC 61439 the routine verification belongs to the assembly manufacturer, and it stays there. What we add is the EN 10204 material certificate for your handover file and a summary of the standards involved.

If the specification calls for a Cuponal busbar profile, that is a different supply route: Cuponal is made by hydrostatic extrusion and exists only as long product (busbar, rod, profile). If you need the Cu-Al transition as a sheet, a disc, a strip or a washer, we supply it in CUPAL.

If it is not cable onto bar but bar onto bar, joining aluminium and copper busbars is the closer page. If the retrofit bolt pattern takes no catalogue part, send us the drawing: DXF, PDF or JPG all work, and we quote within 24 hours.

Questions from panel builders

The bolt gives the thread size, and the conductor cross-section of the lug gives the outer diameter. A 300 mm² lug needs a row whose max. lug cross-section is at least 300 mm². The plain M12 (Ø26 mm) only goes to 240 mm², so it is too small; the M12 (large), Ø30 mm, covers up to 400 mm². SKU ICALCU12CS; the net price per size is on the product page. If the palm is wider than Ø30 mm, step up to the M12 (extra), Ø46 mm.
No, and it cannot. EN 10204 certifies the material (2.2 with every shipment, 3.1 on request); IEC 61439-1 and -2 apply to the finished assembly. The routine verification is carried out and signed by the assembly manufacturer. The CUPAL washer contributes the material and its certificate; it does not verify the joint.
The joint decides. If the lug is already crimped onto the cable and only the bolted interface is dissimilar, the washer is the part: 11 stocked sizes from M6 to M20, 1–2 mm thick depending on size. If the cable end itself has to change from aluminium to copper, use a bimetal lug: the ICALCU range is 109 SKUs from stock, as tubular lugs, inline connectors and pin lugs. On a new connection the bimetal lug puts one contact face fewer into the joint. Once a cabinet has a dozen of these joints, or the bolt pattern matches no catalogue part, a plate cut to your drawing is the simpler answer.
The cross-reference table is on the CUPAL washer product page. NEXANS Cupal M 8 Al-Cu → ICALCU8CS; NEXANS Cupal M 10 Al-Cu and Mentavill 880111 → ICALCU10CS; NEXANS Cupal M 12 Al-Cu → ICALCU12CS2 or ICALCU12CS. The match is by bolt size and nearest outer diameter, so compare the outer diameter with the lug palm before ordering.
Every shipment carries an EN 10204 2.2 test report, which can go into the handover file. An EN 10204 3.1 inspection certificate tied to the batch is available on request; say so with the order. Our supplier works to ISO 9001:2015. EN 10204 certifies the material; IEC 61439 applies to the finished assembly, and the routine verification stays with you as the assembly manufacturer.
With bare aluminium, yes. Rittal's Ri4Power catalogue asks for the oxide layer to be removed, an acid-free grease, the rated torque, a torque check one day later, and then regular thermographic or resistance monitoring of the connections. With a CUPAL washer the bolted faces are like metal on like metal, but keep the post-commissioning torque check and the thermal survey all the same.
Not for the transition, because each face meets its own metal. The CUPAL installation guide asks for clean contact faces with no oil or general-purpose grease; if you want extra moisture protection, use a contact compound made for aluminium joints. In a humid cabinet, also protect the cut edge and the outside of the joint.
All 11 washer sizes and the bimetal lugs are stock items: 2–10 working days from order to delivery. In sheet, the 0.5 and 1.0 mm gauges are in stock; 1.5 and 2.0 mm are made to order, 5–10 working days in production. Every custom outline, and the 500 × 2000 mm format, is quoted within 24 hours; custom cutting takes 5–10 working days in production, and EU door to door is 2–4 weeks.
No. Standard M6–M20 bolted joints and a torque wrench; a spring washer if your detail calls for one. The washers are 1–2 mm thick depending on the size; we confirm the value per part number in the quote, so you can check it against the bolt length of an existing joint. Torque follows the busbar and bolt manufacturers' specification.

Applicable standards for this field

IEC 61439-1
IEC 61439-2
DIN 43671
DIN 43670
MSZ EN 61439-1

Ask an engineer

Application not listed? Describe it and we will advise.