Aluminium cable on a copper busbar in the switchgear cabinet
Where an aluminium feeder lands on a copper busbar. An M6–M20 CUPAL washer, a bimetal cable lug or a transition plate cut to the existing hole pattern, with an EN 10204 2.2 test report on every shipment and 3.1 on request.
You are the one signing the routine verification
The IEC 61439 series splits the work in two. The original manufacturer brings the design verification with a certified system; the assembly manufacturer, the panel builder, puts the cabinet together, carries out the routine verification and signs it. The moment you depart from the certified configuration, the burden of proof moves with you.
There is one joint in that cabinet you cannot verify your way around: the incoming aluminium feeder landing on the copper busbar through a bolted joint. IEC 61439-1 sets a 70 K temperature-rise limit for terminals for external insulated conductors. A direct Al/Cu contact builds an oxide film and, wherever moisture reaches it, starts galvanic corrosion; within a few years the junction can show up as a hot spot on a thermal survey and drift out of that budget under peak load. Antioxidant compound can be re-applied every few years, but that means booking a maintenance window, documenting the work and signing for it.
The trouble does not appear at handover. It appears two or three years later, on a thermographic survey, as a hot spot on a document with your name on it.
In short
In a switchgear cabinet the incoming aluminium feeder meets the copper busbar. If a lug is already crimped on, an M6–M20 CUPAL® bimetal washer goes into the bolted joint, chosen by bolt size and lug cross-section. If the cable end is still free, a bimetal cable lug is the better part. Both ship with an EN 10204 2.2 test report.
- M6–M20
- 11 CUPAL washer sizes
- 1–2mm
- Washer thickness, by size
- 109
- Bimetal cable lug part numbers from stock
- 24h
- Quote for custom geometry
Which washer goes into the joint
Two numbers decide it: the bolt in the joint gives the thread size, and the conductor cross-section of the lug gives the outer diameter you need. Check the palm width separately; if it is wider than the outer diameter of the row you picked, step up to the next outer diameter. Net list prices per size are on the CUPAL washer product page.
| Bolt size | Outer Ø | Max. lug cross-section | SKU |
|---|---|---|---|
| M6 | 16 mm | 120 mm² | ICALCU6CS |
| M8 | 18 mm | 120 mm² | ICALCU8CS |
| M10 | 23 mm | 240 mm² | ICALCU10CS |
| M10 (large) | 26 mm | 300 mm² | ICALCU10CS2 |
| M12 | 26 mm | 240 mm² | ICALCU12CS2 |
| M12 (large) | 30 mm | 400 mm² | ICALCU12CS |
| M12 (extra) | 46 mm | 500 mm² | ICALCU12CS3 |
| M16 | 35 mm | 500 mm² | ICALCU16CS |
| M16 (large) | 46 mm | 630 mm² | ICALCU16CS2 |
| M20 | 37 mm | 500 mm² | ICALCU20CS |
| M20 (large) | 46 mm | 630 mm² | ICALCU20CS2 |
What CUPAL does in the joint
If the bill of materials or the earthing drawing calls for a transition washer between an aluminium bar and a copper lug, first check which part is meant. The same name is used for profiled copper-alloy washers that pierce the oxide film when tightened; that is a different principle and not a bimetal part. The bimetallic vs toothed transition washer comparison shows how to tell them apart. If the specification means a genuine copper-aluminium bimetal disc, pick the row from the table above by bolt size and lug cross-section.
CUPAL puts the whole transition into a single roll-bonded plate or washer, and the rule is the same everywhere: each face meets its own metal. An aluminium lug on a copper bar takes the washer with the aluminium face towards the lug; a copper lug on an aluminium bar takes the same washer the other way up. Either way, the driver of galvanic corrosion, two dissimilar metals sharing an electrolyte at the joint, is removed at the contact itself. No compound goes between the contact faces. Tightening torque remains whatever the busbar and bolt manufacturers specify; CUPAL has no torque table of its own, and the fitting sequence is in the CUPAL installation guide.
If the cable end is still free, a bimetal cable lug does the same job with one contact face fewer, so check that first on a new connection. The bimetal lug or CUPAL washer page sets out the decision.
Net list prices per size, quantity discounts and the distributor cross-reference (NEXANS, Mentavill) are on the CUPAL washer product page.
The base material carries DIN 17007 / DIN 1787 designations (aluminium AL 99.5 / 3.0255, copper E1-Cu58 / 2.0065). Every shipment comes with an EN 10204 2.2 test report; an EN 10204 3.1 inspection certificate is available on request. Our supplier is ISO 9001:2015 certified, and HIDRA-MIX Kft. has been operating in Budapest since 1991.
What this looks like in numbers
Where it fits in the cabinet
Four places in the cabinet where you will meet an Al/Cu joint; the table above gives the SKU for each.
Incoming feeder → main busbar
The problem you need to solve. A three-phase aluminium feeder (e.g. 3×240 mm² Al) lands on the main copper busbar through a bolted lug. Thermally it is one of the hardest-worked joints in the cabinet.
How CUPAL solves it. If the cable is not yet terminated, a bimetal cable lug. If it already carries an aluminium lug, a CUPAL washer or a transition plate cut to the existing pattern between lug and bar, aluminium face to the lug. Torque follows the busbar and bolt manufacturers' specification.
Outgoing feeder: Cu busbar → Al cable to MCC
The problem you need to solve. The outgoing direction lands copper busbar on aluminium cable feeding a motor control centre or sub-distribution. Same Al/Cu bolted joint, often with stricter handover documentation.
How CUPAL solves it. A CUPAL washer between busbar and lug. One part, no extra tools, and the material ships with an EN 10204 certificate you can put in the panel dossier.
N / PE equipotential bar
The problem you need to solve. In a multi-storey riser, aluminium neutral and PE conductors terminate on the cabinet's copper bonding bar. Thermal cycling relaxes the bolted joint and the oxide adds resistance.
How CUPAL solves it. A CUPAL transition plate between bonding bar and riser. Both bolted faces put like metal against like metal, so the joint no longer depends on the aluminium oxide film.
Brownfield retrofit
The problem you need to solve. A 10–20-year-old cabinet gets an aluminium feeder upgrade, but the original copper busbar stays. Catalogue parts do not always fit the old bolt pattern or the stack-up height.
How CUPAL solves it. A CUPAL plate cut to the existing pattern from a DXF, PDF or JPG drawing. Quote within 24 hours, 5–10 working days in production, and it installs without structural modification.
Compared to the usual alternatives
Four familiar approaches to the same bolted joint, how they behave over time, and how much freedom you have on geometry.
| Approach | Joint behaviour over time | Maintenance | Geometry |
|---|---|---|---|
| Cu lug + antioxidant compound on aluminium | Acceptable, drifts over time | Periodic inspection, re-tightening, new compound | Standard lug footprints |
| Bimetal compression lug | Stable; one contact face | Torque check after commissioning | Fixed catalogue geometry; needs a free cable end |
| Over-sized pure copper conductor | No Al/Cu joint | None specific | Removes the joint, but the conductor run is re-specified |
| CUPAL washer or custom-cut plate | Like-for-like faces; cut edge to protect in humid air | Torque check after commissioning | 11 stocked washer sizes, or any outline from DXF, PDF or JPG |
Washer, lug or cut plate
The same material in four forms. The geometry of the joint decides which one belongs in it.
| Form | When this is the one | Geometry | Availability |
|---|---|---|---|
| CUPAL washer (M6–M20) | A finished lug bolts onto the bar and the bolt pattern is fixed | 11 stocked sizes, 1–2 mm thick by size | From stock, 2–10 working days to delivery |
| CUPAL bimetal cable lug (ICALCU) | The cable end itself has to change metal | 109 SKUs; tubular lugs, inline connectors, pin lugs | From stock, 2–10 working days to delivery |
| CUPAL sheet, 500 × 500 mm | Bar-to-bar transition, larger contact area | 0.5 / 1.0 / 1.5 / 2.0 mm | 0.5 and 1.0 mm from stock; 1.5 and 2.0 mm 5–10 working days in production |
| Custom cutting | The existing bolt pattern takes no catalogue part | Any outline from a DXF, PDF or JPG drawing | Quote within 24 h, 5–10 working days in production |
What we supply, and what we don't
We supply into your bill of materials; we do not bid for your work. We do not build cabinets, and we do not sell enclosures, busbar systems, terminal blocks, circuit breakers or installation labour. One line item goes into your BOM: the copper-aluminium transition, as an M6–M20 washer, as an ICALCU bimetal cable lug, 109 SKUs from stock, as CUPAL sheet, 500 × 500 mm, or as an outline cut from your DXF, PDF or JPG drawing. Cutting and punching are done by a partner workshop.
We do not sign the declaration of conformity for the cabinet either. EN 10204 2.2, or 3.1 on request, certifies the material; IEC 61238 and IEC 61439 apply to the assembly the part is fitted into, not to CUPAL itself. Under IEC 61439 the routine verification belongs to the assembly manufacturer, and it stays there. What we add is the EN 10204 material certificate for your handover file and a summary of the standards involved.
If the specification calls for a Cuponal busbar profile, that is a different supply route: Cuponal is made by hydrostatic extrusion and exists only as long product (busbar, rod, profile). If you need the Cu-Al transition as a sheet, a disc, a strip or a washer, we supply it in CUPAL.
If it is not cable onto bar but bar onto bar, joining aluminium and copper busbars is the closer page. If the retrofit bolt pattern takes no catalogue part, send us the drawing: DXF, PDF or JPG all work, and we quote within 24 hours.
Questions from panel builders
Applicable standards for this field
Knowledge base: CUPAL technical articles
4/10/2026
CUPAL bimetal installation and processing guide
Fitting a CUPAL bimetal washer step by step: surface prep, which face goes where, torque and edge protection outdoors. Plus the 260 °C / 4 h processing limit.
Read the full article →5/13/2026
EN 10204 2.2 certificate meaning: 2.2 vs 3.1
EN 10204 type 2.2 is a generic test report, type 3.1 a lot-specific inspection certificate. What each means, when you need which, and how to request one.
Read the full article →3/1/2026
Can copper and aluminium touch? Galvanic corrosion
They can touch, but where moisture reaches the joint the aluminium corrodes: 0.55 V apart in practice. What fails, and the bimetal washer that stops it.