GuidesSeptember 8, 202615 min read

CUPAL part number cross-reference: which size matches your code?

This page maps the designations that turn up on drawings, BOM lines and old purchase orders onto the CUPAL® sizes we supply: distributor codes such as 880111, ICALCU10CS, Cupal M 10 Al-Cu, VCUP2 and 1053, and parts from other brands with the same format, from DEHN, nVent ERIFLEX, BTicino, Klauke and Helukabel. Bore, outer diameter, thickness and our SKU sit on the same row. Net list prices are on the product pages, one link away.

In short

Distributor codes (880109–880112, Cupal M 10 Al-Cu, ICALCU10CS, VCUP1, VCUP2, 1053) and same-format parts from DEHN, nVent ERIFLEX, BTicino, Klauke and Helukabel, mapped to the CUPAL size we supply, with bore, outer diameter, thickness and SKU on one row. Matches are by dimensions only. Where we have no stock size, the row says so.

M6–M20
11 stocked washer sizes
1–2mm
Washer thickness
2–10working days
Washer lead time
24h
Quote turnaround

Same format from other brands: DEHN, nVent ERIFLEX, BTicino, Klauke, Helukabel

The parts below come from other manufacturers and have the same format as a CUPAL size we supply. They are matched by dimensions only, using each maker's own datasheet or catalogue. Same format is not the same construction: Klauke and Helukabel describe their discs as E-Al, copper-plated on one side, while CUPAL is copper roll-bonded onto aluminium, 70/30 by layer thickness. A row here does not make our part an approved replacement in a specification that names the other brand; if yours does, send it and we check it with you before you order.

Other brand, part no.Their published dimensionsSame format in CUPALNote
DEHN 562 440 (CUPAB 500X40X0.5)Strip 500 × 40 × 0.5 mm, Al/CuCUPAL strip 500 × 40 × 0.5 mm, from stockDEHN states no layer ratio
DEHN 562 460 (CUPAB 500X60X0.5)Strip 500 × 60 × 0.5 mm, Al/CuCUPAL strip 500 × 60 × 0.5 mm, cut to order5–10 working days production
nVent ERIFLEX BMS500 (553090)Plate 500 × 500 × 1 mm: 0.7 mm Al + 0.3 mm CuTCUP10 sheet 500 × 500 × 1.0 mm, from stockSame nominal layer split, 0.70 / 0.30 mm
nVent ERIFLEX BMS100 (553080)Plate 100 × 100 × 1 mm: 0.7 mm Al + 0.3 mm CuCUPAL plate 100 × 100 × 1.0 mmCut from 1.0 mm sheet
BTicino 030009CUPAL plate 60 × 60 mm, cast-resin transformer accessoryCUPAL plate 60 × 60 mmBTicino gives no thickness: measure the old plate or ask the transformer maker
BTicino 030014 / 030008 / 030010 / 030011 / 030012Plates 40 × 40, 50 × 50, 80 × 80, 100 × 100, 120 × 120 mmCUPAL plates in the same sizesThickness as above
Klauke CS615M6, bore 6.5, OD 15, 2 mmM6, 6.4 / 16 mm, ICALCU6CSOur OD is 1 mm larger
Klauke CS818 · Helukabel 906049M8, bore 8.5, OD 18; Klauke 2 mm, Helukabel 1 mmM8, 8.4 / 18 mm, ICALCU8CSOur thickness per part number is confirmed in the quote; against a 1 mm part, check the bolt length
Klauke CS1022 · Helukabel 906050M10, bore 11, OD 22, 2 mmM10, 10.5 / 23 mm, ICALCU10CSOur OD is 1 mm larger
Klauke CS1228 · Helukabel 906051M12, bore 13, OD 28, 2 mmM12, 13 / 26 mm or 13 / 30 mmThe lug palm decides: 26 mm up to 240 mm², 30 mm up to 400 mm²
Klauke CS1428 · Helukabel 906052M14, bore 15, OD 28, 2 mmNo stock sizeCut to your drawing by our partner
Klauke CS1635 · Helukabel 906053M16, bore 17, OD 35, 2 mmM16, 17 / 35 mm, ICALCU16CSSame bore and outer diameter

All dimensions in mm, as published by the manufacturers when we checked them in November 2026: DEHN 562 440, DEHN 562 460, nVent ERIFLEX BMS, BTicino 030009 and the BTicino cast-resin transformer catalogue, Klauke Cupal discs, Helukabel KAC-U.

Klauke and Helukabel restrict their discs to dry environments; Klauke also allows them with tinned aluminium lugs in humid ones. A CUPAL part has the same weak point at its cut edge, where the bond line is exposed: outdoors or in humid conditions, protect or cover the edge and ask us before you specify.

Washer part numbers: which CUPAL washer they match

The four-digit 880109 / 880110 / 880111 / 880112 family, the Cupal M 6/8/10/12 Al-Cu designations and the ICALCU10CS-style codes all describe the same class of part: a roll-bonded copper-aluminium disc that sits in a bolted joint so that each conductor touches only its own metal. The table maps each string to the size we stock, using our own dimensions rather than any third party's. One name does not belong in that family: where a drawing says only transition washer, it can also mean a profiled copper-alloy washer, which is copper alloy throughout. How a bimetallic washer differs from a toothed one settles which part the line item is asking for before you match a code to it.

Designations that appear on distributor listings and drawings, against the CUPAL washer we hold for each. Lead time 2–10 working days.

Designation you have880109
Also appears asCupal M 6 Al-Cu
Our bore / outer Ø / thickness6.4 / 16 / 2 mm
Our sizeM6
Our SKUICALCU6CS
Designation you have880110
Also appears asCupal M 8 Al-Cu
Our bore / outer Ø / thickness8.4 / 18 / 2 mm
Our sizeM8
Our SKUICALCU8CS
Designation you have880111
Also appears asCupal M 10 Al-Cu · EAN 8591120057484
Our bore / outer Ø / thickness10.5 / 23 / 2 mm
Our sizeM10
Our SKUICALCU10CS
Designation you have880112
Also appears asCupal M 12 Al-Cu
Our bore / outer Ø / thickness13 / 26 or 30 / 2 mm
Our sizeM12 or M12 (large)
Our SKUICALCU12CS2 / ICALCU12CS
Designation you haveICALCU10CS
Also appears asMfr-Nr 180082 · EAN 8014212184290
Our bore / outer Ø / thickness10.5 / 23 / 2 mm
Our sizeM10
Our SKUICALCU10CS
Designation you haveICALCU10CS2
Also appears as—
Our bore / outer Ø / thickness10.5 / 26 / 2 mm
Our sizeM10 (large)
Our SKUICALCU10CS2
Designation you haveICALCU12CS2
Also appears as—
Our bore / outer Ø / thickness13 / 26 / 2 mm
Our sizeM12
Our SKUICALCU12CS2
Designation you haveICALCU12CS
Also appears as—
Our bore / outer Ø / thickness13 / 30 / 2 mm
Our sizeM12 (large)
Our SKUICALCU12CS

Confirm before ordering. The rows are mapped by bolt size and nearest outer diameter. The bolt sets the bore, but the lug palm sets the outer diameter, so check it against your lug first. 880112 is usually published at Ø28 mm, which falls between our M12 at 26 mm and our large M12 at 30 mm; the lug decides, and the threshold is the cross-section it is crimped onto: up to 240 mm² take the 26 mm (ICALCU12CS2), 240–400 mm² take the 30 mm (ICALCU12CS). Every dimension in the table is ours, and published figures for these designations disagree with each other; see check 3 below before you order to a drawing.

The distributor codes above stop at M12. Our range does not: the full washer range with net list prices runs to 11 stocked sizes, 16–46 mm outer diameter, for lugs up to 630 mm². The priced rows can be linked directly: ICALCU6CS, ICALCU8CS, ICALCU10CS, ICALCU10CS2, ICALCU12CS2 and ICALCU12CS. Every row there carries a quantity field that builds the enquiry for you.

Sheet part numbers: the VCUP and HI-CUP designations

VCUP1 and VCUP2 designate a 500 × 500 mm CUPAL sheet in 0.5 mm and 1.0 mm; the same two sheets circulate on Hungarian and German BOM lines as HI-CUP-0.5 and HI-CUP-1.0. That is the same sheet we supply as TCUP05 and TCUP10, orderable directly at the net list price shown on the product page. A sheet is a larger commitment than a washer, so confirm the thickness before you order.

Sheet designations against the CUPAL sheet we supply, with availability per 500 × 500 mm sheet. The 1.5 and 2.0 mm thicknesses have no distributor equivalent; they are ours, made to order.

Designation you haveVCUP1
Also appears asHI-CUP-0.5
Size500 × 500 × 0.5 mm
Our SKUTCUP05
AvailabilityIn stock
Designation you haveVCUP2
Also appears asHI-CUP-1.0
Size500 × 500 × 1.0 mm
Our SKUTCUP10
AvailabilityIn stock
Designation you have—
Also appears as—
Size500 × 500 × 1.5 mm
Our SKUTCUP15
AvailabilityMade to order, 5–10 working days
Designation you have—
Also appears as—
Size500 × 500 × 2.0 mm
Our SKUTCUP20
AvailabilityMade to order, 5–10 working days

The material is 70 % aluminium (AL 99.5, Werkstoff-Nr. 3.0255) over 30 % copper (E1-Cu58, Werkstoff-Nr. 2.0065), bond strength 70–110 N/cm; the full figures are in the technical datasheet. Net list prices and quantity fields are on the product page: TCUP05 and TCUP10. The 500 × 2000 mm format and any other geometry are quoted within 24 hours rather than list-priced.

Strip part numbers, and where we cannot ship from stock

The J. Pröpster designation 1053 is a 500 × 40 mm bimetal strip, typically used for a lightning-protection transition; it also appears under distributor SKUs such as JPR1053. It is the one code on this page we cannot supply from stock. Our stock strip is 500 × 40 × 0.5 mm; 1053 is normally published at 0.8 mm.

DesignationPublished asWhat we can supply
1053500 × 40 × 0.8 mm (0.5 mm also appears)Not in 0.8 mm. The same width cut to order in 0.5 or 1.0 mm

Two things follow. First, we have no 0.8 mm gauge: CUPAL sheet comes in 0.5, 1.0, 1.5 and 2.0 mm. If 0.5 or 1.0 mm suits the joint, our partner cuts the strip to order in the same 40 mm width: quote within 24 hours, 5–10 working days of production. In 0.5 mm, the 500 × 40 × 0.5 mm stock strip is the same size and ships from stock. Second, the published thickness for this code disagrees across sources: 0.5 mm and 0.8 mm both appear against it, and 0.5 against 0.8 is a 60 % difference in section, not a rounding error. Measure the part you already have, or send us the drawing, and we confirm the thickness before anything is cut.

Cable-lug part numbers: how to read an ICALCU code

There are 109 lug SKUs, so instead of listing them all, here is how to read your own code. A tubular lug is ICALCU<cross-section><bolt>, so ICALCU24016 is 240 mm² for an M16 bolt. An inline connector is ICALCU<Al><Cu>V: ICALCU1610V joins a 16 mm² aluminium conductor to a 10 mm² copper one, and connectors carry no bolt size at all. A pin lug is ICALCU<Al>B<pin Ø>V, so ICALCU95B12V is 95 mm² with a Ø12 mm copper pin. Tubular lugs cover 10–625 mm² with M8 to M20 bolt holes, to DIN 46329; inline connectors join Al 16–500 mm² to Cu 10–400 mm²; pin lugs stop at 300 mm² and Ø18 mm. Codes ending in CS are not lugs but washers; those are in the table further up. Decode the string, then find the row in the full ICALCU cable-lug range.

How to confirm it really is the same part

A matching code is a lead, not a confirmation. Four checks settle it, in this order.

1. Start with the bolt size

The bore has to match the bolt, and nothing else about the joint changes that. An M10 bolted joint takes an M10 washer, whatever the catalogue calls it. If your source publishes no bore at all (and many of the Hungarian listings carrying the four-digit codes publish no dimensions whatsoever), the M-size in the description is the only thing you can rely on from it.

2. Check the outer diameter against the lug palm

This is where two parts with the same M-size stop being interchangeable. The washer has to cover the whole contact face of the lug, not just the ring around the bolt, so measure the palm and pick the outer diameter that covers it. That is why 880112 maps to two of our SKUs: our M12 exists at 26 mm for lugs up to 240 mm² and at 30 mm for 240–400 mm². The full washer range lists the maximum lug cross-section against every outer diameter.

3. Treat the published dimensions as figures to confirm, not to assume

Our washers are 1–2 mm thick depending on the size, and we confirm the value per part number in the quote. Published figures for the same designation do not agree with one another. Against the M10 codes you will find both 10.5 mm and 11 mm bore, both Ø23 and Ø26 mm outer diameter, and both 1 mm and 2 mm thickness, including under the manufacturer number and EAN printed on the ICALCU10CS row above, which lead to listings giving 1 mm or 2 mm. Against the 1053 strip, both 0.5 mm and 0.8 mm appear. Every figure in the tables above is ours. If your drawing or your existing stock is specific, measure the part or send us the drawing, and we confirm against it before you order rather than after.

4. Decide what certificate you need

An EN 10204 2.2 material certificate ships with every order as standard, and 3.1 is available on request. If you are replacing a part originally bought elsewhere and the specification calls for documented material, ask for 3.1 when you request the quote. It has to be ordered with the goods; whether one can still be supplied after delivery is confirmed case by case. The difference between the two grades is set out in the EN 10204 material certificate article.


Can't find your part number? Send us the designation and the drawing, and we confirm within 24 hours which of our sizes matches it, or have it cut to size from your drawing if none does. Get in touch.

Part number questions

For the joint, yes. Both designate a copper-aluminium bimetal washer for an M10 bolt, and both map to the same part in our range, ICALCU10CS. Confirm the dimensions before you order. Ours is 10.5 mm bore and 23 mm outer diameter, and we confirm the thickness for this part number in the quote; published figures for these designations disagree, with one source giving Ø23 × 2 mm and another Ø26 × 1 mm against the same code. If your drawing fixes an outer diameter or a thickness, send it and we confirm before you order.
Because the code identifies a part family, not a fully dimensioned specification, and the listings that carry these codes rarely publish a datasheet to reconcile against. For the same designation you will find both 1 mm and 2 mm quoted, and for the 1053 strip both 0.5 mm and 0.8 mm. Our figures are on this page and on the product pages. Where your source disagrees with ours, measure the part or send us the drawing; we would rather resolve it before the order than after.
The designation itself, plus whatever you have of the bolt size, bore, outer diameter, thickness and the cable cross-section of the lug it sits under. A photo of the old part next to a rule is enough in most cases. If you have a drawing in DXF, PDF or JPG, send that instead and we work from it directly.
We can certify what we supply, not what another supplier shipped. If you replace the part with the equivalent from our range, an EN 10204 2.2 material certificate ships with the order as standard and a 3.1 inspection certificate is available on request. Ask for 3.1 when you request the quote so it is arranged with the order.
We quote small quantities of washers too; order quantity and pack size are confirmed in the quote. Custom cutting is different: the minimum there is one 500 × 500 mm board, from which several pieces can usually be cut depending on the shape.
Washers, the 0.5 mm and 1.0 mm sheets and the 500 × 40 × 0.5 mm strip come from stock, 2–10 working days from order to delivery. The 1.5 mm and 2.0 mm sheets are made to order in 5–10 working days. Anything cut to size, including a non-stock strip thickness, is quoted within 24 hours and produced in 5–10 working days.
It has the same format, not the same construction. Klauke CS1022 and Helukabel 906050 are published at 11 mm bore, 22 mm outer diameter and 2 mm thickness; our M10 is 10.5 / 23 mm, so it fits the same M10 joint with a slightly larger contact face. Theirs are E-Al copper-plated on one side, ours is 70/30 roll-bonded CUPAL. If a specification names the brand, check with whoever owns it before substituting.
Yes. DEHN 562 440 is a 500 × 40 × 0.5 mm Al/Cu strip, and our stock CUPAL strip has the same dimensions. The 500 × 60 × 0.5 mm format of DEHN 562 460 is cut to order in 5–10 working days.
No. Cupal M 10 Al-Cu is a designation for the same thing this whole page is about, a copper-aluminium bimetal washer for an M10 bolt. The Al-Cu in the name simply spells out the two metals. Catalogues also call it a transition washer, a bimetallic washer or an Al/Cu washer. Watch one distinction only, because transition washer is also used for a different part, namely profiled copper-alloy washers, which are copper alloy throughout and not a bimetal. Our comparison of the bimetallic and the toothed transition washer, linked from the washer section above, sets the two side by side if your drawing is ambiguous.

Have a question?

Email us or use the form: we reply within 24 hours on working days.

Get a Quote