Cast-resin transformers · LV terminals · Substations

Dry-type transformers: copper cable and busbar on aluminium terminals

The low-voltage terminals of cast-resin (dry-type) transformers are often aluminium. Between a copper lug or copper busbar and an aluminium terminal goes a bimetal plate or washer, as the transformer makers' installation instructions require.

In short

The low-voltage terminals of cast-resin transformers are often aluminium. A copper lug or busbar on such a terminal needs a copper-aluminium bimetal plate or washer between them, aluminium face to the terminal. The SGB-SMIT and Hammond installation instructions both call for this. We supply the CUPAL® plate cut to the terminal's size and hole pattern.

0.5–2.0mm
CUPAL sheet the plate is cut from
M6–M20
Washers, 11 sizes from stock
5–10working days
Production of cut plates
24h
Quote

Why an aluminium terminal needs a transition

Many makers of dry-type, cast-resin distribution transformers wind them in aluminium. A technical note on myelectrical.com states that Siemens GEAFOL transformers use aluminium for both the LV and the HV windings, and describes a site where copper cable was terminated on the transformer's aluminium terminals with bimetallic plates inserted between lug and terminal. The SGB-SMIT operating manual for cast-resin transformers also says the transformer's electrical terminals may be made of aluminium or of copper.

On the LV side the continuous current is high, the joint heats and cools with the transformer, and the substation is not opened for years. If a copper lug or copper busbar goes straight onto an aluminium terminal, an insulating oxide film grows on the aluminium, and wherever moisture is present the two metals form a galvanic cell. Bolt preload drops over the thermal cycles, contact resistance rises and the joint runs warm.

What the transformer makers specify

The makers' installation instructions agree: a bimetal transition goes between aluminium and copper.

Maker, documentWhat it specifies
SGB-SMIT, Operating Manual for cast resin transformers (Rev. I, 20.02.2024), section 9.4 Phase terminalsInsert a copper-plated aluminium sheet between the copper/aluminium contact surfaces, with the copper-plated side against the copper terminal. Polish the contact surfaces metallically bright, again every time the contact is opened. On the aluminium side, add a washer to ISO 7093 in the threaded connection.
Hammond Power Solutions, ISOCAST cast-resin transformers, installation manualLV connections are made with tinned copper lugs. For connection to the aluminium LV terminals through copper busbars, Hammond can provide Cupal plates or tinned LV terminals on request.
Hammond Power Solutions, VPI transformers, installation manual (German)Connections between aluminium and copper busbars are to be made with CUPAL intermediate plates.
BTicino (Legrand), installation accessories for cast-resin transformers030009 "Piastrina CUPAL 60 x 60mm": a 60 × 60 mm bimetal plate, referencing CEI EN 60076-11.
Schneider Electric, TRIHAL FAQThe neutral point is standardised as a copper bar with bimetal washers. The phase connector plates are tinned aluminium, so according to Schneider bimetal terminals are not necessary for connecting the power cables.

In short, your transformer's own manual decides. Where it calls for a bimetal plate or washer, that is what we supply; where the maker says a tinned terminal needs none, you need none. We have no partnership with any of these manufacturers; we cite their documents as sources.

CUPAL is cold roll-bonded copper-aluminium bimetal, exactly the copper-clad aluminium sheet these instructions describe. We supply a CUPAL plate cut to fit the terminal from your drawing: to the terminal width, the hole pattern and the thickness you need. If a single bolt holds the joint, for example on the neutral bar, a CUPAL washer, M6–M20, is enough, with an outer diameter that covers the lug palm.

Which part for which terminal

The transformer's installation manual comes first. If it asks for a bimetal transition, this table helps you choose the form.

JointAluminium phase terminal → copper busbar
PartCUPAL plate cut to drawing
NoteCut to the terminal width and hole pattern, aluminium face to the terminal
JointAluminium phase terminal → several copper cable lugs
PartCut CUPAL plate covering all the lug palms
NoteOne plate, one contact face on the terminal
JointNeutral bar or a single-bolt joint
PartCUPAL washer M6–M20
NoteThe outer diameter should cover the lug palm
JointAluminium cable with a free end → copper terminal
PartBimetal cable lug (ICALCU), 10–625 mm²
NoteThe transition sits in the lug body
JointTinned aluminium terminal where the maker says no transition is needed
PartNo CUPAL needed
NoteFollow the transformer manual

How the joint is built

1

Check the manual

Look up in the transformer's installation manual whether the terminal is aluminium or copper, and whether it calls for a bimetal interlayer.

2

Clean the faces

Polish the contact surfaces to bright metal just before assembly, and make sure no metal dust is left on the transformer. SGB-SMIT asks for this again every time the contact is opened.

3

Orient the plate

Aluminium face to the aluminium terminal, copper face to the copper lug or bar. The copper face is reddish, the aluminium face silver.

4

Assemble the bolted joint

In the SGB-SMIT drawing the joint consists of the bolt, a conical spring washer, an ISO 7093 washer on the aluminium side, the aluminium bar, the copper-clad aluminium sheet, the copper bar and the nut. Keep oil and general-purpose grease off the contact faces.

5

Tighten to the maker's torque

The torque comes from the transformer maker's table, by bolt size and bolt material. CUPAL has no torque table of its own.

What to send with your enquiry

  • the terminal width and thickness, the hole diameter and spacing, or a dimensioned drawing (DXF, PDF, JPG);
  • whether a copper busbar or cable lugs go on it, and how many lugs per terminal;
  • the quantity per transformer and the number of transformers.

We quote within 24 hours. Plates take 5–10 working days in production, and EU door to door is 2–4 weeks; washers and bimetal lugs are stock items, 2–10 working days from order to delivery. Custom cutting has a minimum of one 500 × 500 mm sheet. A partner workshop does the cutting. Every shipment comes with an EN 10204 2.2 test report, and an EN 10204 3.1 inspection certificate on request.

Hammond rates its standard ISOCAST transformers for indoor installation in clean, dry rooms. If your substation is humid or outdoors, tell us: at the cut edge of the plate the Al/Cu bond line is exposed, and in that environment it needs protection too. If it is not the transformer terminal but the receiving switchboard where an aluminium bar meets a copper bar, joining aluminium and copper busbars is the closer page.

Request a quote with your terminal dimensions

Questions from transformer installers

The transformer maker decides. Schneider Electric states for its TRIHAL transformers that the phase connector plates are tinned aluminium, so bimetal terminals are not necessary for connecting the power cables, while the neutral copper bar comes with bimetal washers. SGB-SMIT, by contrast, specifies a copper-plated aluminium sheet for every copper-aluminium connection. Check your own transformer's manual.
If a copper busbar or several lugs go on the terminal, a plate: it covers the whole contact face and is cut to the terminal's hole pattern. If a single bolt holds one lug, for example on the neutral bar, a washer is enough, with an outer diameter that covers the lug palm, M6 to M20 from stock.
The terminal decides, not the catalogue. BTicino, for example, sells a 60 × 60 mm CUPAL plate for its own cast-resin transformers. The plate is cut to the terminal width and hole pattern, so you do not have to hunt for a ready-made size. Send the terminal drawing or its dimensions.
The aluminium face goes to the aluminium terminal, the copper face to the copper lug or bar. The SGB-SMIT manual says the same: the copper-plated side rests against the copper terminal.
SGB-SMIT specifies contact surfaces polished metallically bright, repeated every time the contact is opened. The CUPAL installation guide says to keep oil and general-purpose grease off the contact faces, and if a compound is used, to use one made for aluminium joints. If your transformer maker specifies something else, that applies.
No. We are not a partner of any transformer maker. The makers' instructions describe the interlayer material (copper-plated aluminium sheet, Cupal plate, CUPAL plate), and that is the material we supply, cut to your terminal, with an EN 10204 material certificate.
IEC 60076-11 is the standard for dry-type transformers; it applies to the transformer, not to an interlayer plate. The CUPAL plate ships with a material certificate (EN 10204 2.2 test report, 3.1 on request), not with a product certificate.

Applicable standards for this field

IEC 60076-11
IEC 61439-1

Ask an engineer

Application not listed? Describe it and we will advise.